AUMA FQM 05.1 - Review and Validation of the Safe End Position Feedback Safety Function

AUMA FQM 05.1
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
Safe OPENING
(ESD in direction fail safe position OPEN)
Configuration
Safe CLOSING
(ESD in direction fail safe position CLOSED)
FQM starts automatic initialisation (spring is wound) FQM starts automatic initialisation (spring is wound)
Yes
No
Check FS module signal behaviour:
Once initialisation is complete, the fail safe fault signal
changes to:
FS failure NC (NC contact) output = open
(FS ready signal)
Time measurement complete, 2 minutes not ex-
ceeded.
Yes
No
Check FS module signal behaviour:
Once initialisation is complete, the fail safe fault signal
changes to:
FS failure NC (NC contact) output = open
(FS ready signal)
Time measurement complete, 2 minutes not ex-
ceeded.
= Executed
Yes = Condition met
No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
Additional proof test checklist for version or configuration:
Safe ESD function:Safe CLOSING" (Safe ESD in direction CLOSE) with addi-
tional tripping in case of mains failure
Safe ESD function: Safe OPENING" (Safe ESD in direction OPEN) with addi-
tional tripping in case of mains failure
Irrespective of type of seating
Table 11: Additional proof test checklist
Configuration
Safe OPENING with additional tripping in case of
mains failure
(ESD in direction fail safe position OPEN)
Configuration
Safe CLOSING with additional tripping in case of
mains failure
(ESD in direction fail safe position CLOSED)
1. Actuator in end position CLOSED? 1. Actuator in end position OPEN?
2. Fail safe fault signal?
FS failure NC (NC contact) output = open
(FS ready signal)
2. Fail safe fault signal?
FS failure NC (NC contact) output = open
(FS ready signal)
3. Power supply (mains) of FQM interrupted?
(execute operating time measurement)
3. Power supply (mains) of FQM interrupted?
(execute operating time measurement)
Yes
No
Check reaction of fail safe unit:
FQM operates in direction OPEN? (start of operating
time measurement)
Yes
No
Check reaction of fail safe unit:
FQM operates in direction CLOSE? (start of operating
time measurement)
Yes
No
FQM reaches end position OPEN? (Operating time
measurement complete.)
Yes
No
FQM reaches end position CLOSED? (Operating time
measurement complete.)
Yes
No
FQM operating time corresponds to indications on
name plate for 90° swing angle or the configured op-
erating time?
Operating time [50 %/+ 100 %]
Yes
No
FQM operating time corresponds to indications on
name plate for 90° swing angle or the configured op-
erating time?
Operating time [50 %/+ 100 %]
Yes
No
Check FS module signal behaviour:
Fail safe fault signal?
FS failure NC (NC contact) output = close
(FS fault signal)
Yes
No
Check FS module signal behaviour:
Fail safe fault signal?
FS failure NC (NC contact) output = close
(FS fault signal)
4. Power supply (mains) of FQM restored? Start of
time measurement.
4. Power supply (mains) of FQM restored? Start of
time measurement.
FQM starts automatic initialisation (spring is wound) FQM starts automatic initialisation (spring is wound)
Yes
No
Check FS module signal behaviour:
Once initialisation is complete, the fail safe fault signal
changes to:
FS failure NC (NC contact) output = open
(FS ready signal)
End of time measurement, 2 minutes were not ex-
ceeded.
Yes
No
Check FS module signal behaviour:
Once initialisation is complete, the fail safe fault signal
changes to:
FS failure NC (NC contact) output = open
(FS ready signal)
End of time measurement, 2 minutes were not ex-
ceeded.
10.2.2. Review and validation of the Safe end position feedback safety function
Proof test checklist for execution or configuration of one of the subsequent safety
functions:
34