AUMA FQM 05.1 - FQM Diagnostic Operation Counter Checklist

AUMA FQM 05.1
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
Fail safe position OPEN and CLOSED (safety position OPEN and CLOSED)
Yes
No
check FQM end position switch:
End position OPEN not reached signal (output signal inactive), i.e.:
LSO 38-20=NC output (NC contact) = closed
LSO 19-21=NO (NO contact) output = open
End position CLOSED not reached signal (output signal inactive), i.e.:
LSC 35-23=NC output (NC contact) = closed
LSC 22-24=NO (NO contact) output = open
No fail safe fault signal may be present (FS ready signal).
= Executed
Yes = Condition met
No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
10.2.3. FQM diagnostic operation counter checklist
When using the ESD safety function, this test must be done for each proof test test
once the ESD function has been tested.
Table 13: Test sequence checklist
Test
Counter of FQM diagnostic operations within the AC .2 actuator controls.
1. Note the value of parameter FQM count. diagn. op. (PRM_5263) in the Diagnostic>FQM menu.
2. Start internal diagnostics of the FQM by operating the FQM from the end position opposite the safety end position
(i.e. for fail safe CLOSE from end position OPEN).
Yes
No
3. Has the value of parameter FQM count. diagn. op. (PRM_5263) in the Diagnostic>FQM menu been incremented
by one?
= Executed
Yes = Condition met
No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
36