8.1 Connection with AUMA plug/socket connector (S, SH, SE)
Before mains connection
Check whether type of current, supply voltage, and frequency comply with
motor data (refer to name plate at motor):
Opening the terminal compartment
.
Loosen bolts (1) and remove cover (figure 15).
.
Loosen screws (2) and remove socket carrier from cover.
.
Insert cable glands suitable for connecting cables
(The enclosure protection stated on the name plate is only ensured if
suitable cable glands are used.)
.
.
.
Seal cable entries which are not used with suitable plugs.
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1/AM 02.1 Operation instructions
16
Figure12: Version S (standard) Figure 13: Version SH Figure 14: Version SE
VD00 63-4/45
Art. No.: Z006.413
3 ~ 400V 60Hz
0.09 kW
Y 0.60A
Current type/mains voltage/mains frequency
Figure 15: Opening the terminal compartment
Cover
(1)
Socket carrier
(2)
Cable gland and
screw plug
in enclosure protection
according to name plate
IP67
Thermal protection: Th
Insulation class: F
Enclosure protection