21.2.1 Setting type of signal (option)
The signal type (current/voltage signal) of nominal value E1 and actual
value E2 is set in the factory and marked with a label on the cover plate of
the positioner (refer to figure 47).
For split range version (page 38) and for versions with a setpoint
E1 0/4 20 mA, it is possible to change the type of signalling. For these
versions, the positioner board is equipped with an additional switch S1-7:
If the setting is subject to subsequent change, the marking also has to be
changed. Furthermore, the wiring diagram indicated on the name plate of
the actuator controls also changes (see page 56).
36
Multi-turn actuators SAExC 07.1 SAExC 16.1/SARExC 07.1 SARExC 16.1
with actuator controls AUMA MATIC AMExC 01.1 Operation instructions
Figure 48: Positioner board A7
V28
V27
V18
V10
P10
MP2(+)
MP1(–)
Meas. points: MP3(+)/MP4(–) for E1
P9 (ΔE)
P7 (Sens)
P3 (0)
P4 (max)
S2-7
S3-7
E2{
Meas.
points:
Programming
Command signal
Setpoint E1
Feedback
Actual value E2
1)
via DIP switch S1-7
(see figure 48)
4–20mA
0–20mA
4–20mA
0–20mA
4–20mA
0–20mA
0–5V
0–5V
4–20mA
0–20mA
0–5V 0–5V
0–10V
4–20mA
0–20mA
0–10V 0–5V
1) Signals for internal feedback:
0/4 20 mA from electronic position transmitter
or0–5Vfrom precision potentiometer 5 k Ω
Table 6: Possible settings