Diagnostic M0022
TMS proof test M1950
Test procedure:
1. Set selector switch to position 0 (OFF).
2.
Return to the main menu and select the simulation value in parameter TMS
proof test M1950: Select Thermal test.
3.
Activate motor protection simulation: Press Ok push button.
The safety function is correct if no fault signal is displayed.
4.
Reset simulation: Press Ok push button or exit the simulation menu and reset
the selector switch to its initial position.
80
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2 Control unit: electronic (MWG)
Corrective action ACExC 01.2 Non-Intrusive Profinet