4. Operate valve into opposite end position.
➥
The value set in end position (0/4 mA or 20 mA) does not change during travel in
setting mode.
5. Perform setting in the second end position following the same steps.
6. Approach both end positions again to check the setting.
→
If the measuring range cannot be set:
Refer to <Faults during commissioning>.
→
If the current values (0/4/20 mA) are incorrect:
Refer to <Current values: adjust>.
→
If the current value fluctuates (e.g. between 4.0 – 4.2 mA):
Switch off LED end position signaling.
Refer to <LED end position signaling: switch on/off>.
9.6.2. Current values: adjust
The current values (0/4/20 mA) set in end positions can be adjusted at any time.
Conventional values are e.g. 0.1 mA (instead of 0 mA) or 4.1 mA (instead 4 mA).
Information If the current value fluctuates (e.g. between 4.0 – 4.2 mA), the <LED end position signal-
ing> must be switched off for current adjustment.
→
Operate valve in desired end position (OPEN/CLOSED).
→
Reduce current value: Press push button [S1]
(the current is reduced by 0.02 mA every time the push button is pressed)
→
Increase current value: Press push button [S2]
(the current is increased by 0.02 mA every time the push button is pressed)
9.6.3. LED end position signaling: switch on/off
The LED behavior for end position reached can be set as follows: blinking/continuous
illumination or no illumination. During setting mode, end position signaling is switched
on.
Switching on and off
1. Operate valve in one of the end positions (OPEN/CLOSED).
2. Hold down push buttons [S1] or [S2] for approx. 3 seconds.
➥
End position signaling is switched on or off.
Table 9:
LED behavior when end position signaling is switched on
LED behavior in end positionSet output current
LED is blinking slowly
4 mA
LED is blinking fast
0 mA
LED is illuminated
20 mA
9.7. Potentiometer
— Option —
The potentiometer is used as travel sensor and records the valve position.
Setting elements
The potentiometer is housed in the actuator switch compartment.The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via potentiometer [1].
36
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2
Commissioning