10. Operation and indications of the local controls
Selector switch
Position OFF (0):
- No remote control possible
- No local control possible
- Actuator remains ready for signalisation
signalisation (the controls’ power supply is maintained)
Position Local control (I):
The actuator can be operated locally via the push buttons
OPEN - STOP - CLOSE.
Position Remote control (II):
The actuator can be controlled from remote, e.g. via the
control room.
Position Test (III):
Test PTC tripping device (refer to page 26)
Only available in combination with motor protection
(PTC thermistor).
Red indication light (fault) is illuminated.
Position Reset (III):
Reset fault signal (red indication light) after the motor pro
-
tection has tripped (refer to page 49).
Only available in combination with motor protection
(PTC thermistor).
19
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
Operation instructions with actuator controls AUMA MATIC AM 01.1/AM 02.1
Figure 22: Local controls
Selector switch
Push buttons
Indication lights
I
I
0
I
I
0
I
I
0
Rese
t
ΙΙΙ
Te st
ΙΙΙ
Ι
ΙΙ
0
Te st
ΙΙΙ
Rese
t
Ι
ΙΙ
ΙΙΙ
0

Table of Contents