17. Setting the electronic position transmitter RWG (option)
— For remote indication or external control —
After mounting the actuator on the valve, check setting and adjust, if neces
-
sary (refer to subclauses 17.1 or 17.2).
The position transmitter board (figure 38) is located under the cover plate
(figure 39).
28
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1/AM 02.1 Operation instructions
Terminal plans
KMS TP_ _ 4 / _ _ _
3- or 4- wire system
KMS TP _ 4 _ / _ _ _
KMS TP _ 5 _ / _ _ _
2-wire system
Output current
I
a
0 – 20 mA, 4 – 20 mA 4 – 20 mA
Power
supply
U
v
24 V DC, ±15 %
smoothed
14 V DC + (I x R
B
),
max. 30 V
Max. input
current
I
24 mA at 20 mA
output current
20 mA
Max. load
R
B
600 W (Uv - 14 V)/20 mA
Table 3: Technical data RWG 4020
Figure 38: Position transmitter board