EasyManua.ls Logo

AUMA SAR 07.6 - Industrial Ethernet Cable: Connect; Accessories for Electrical Connection; Actuator Controls on Wall Bracket

AUMA SAR 07.6
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3.4. External earth connection
Figure 30: Earth connection for multi-turn actuator
Application
External earth connection (U-bracket) for connection to equipotential compensation.
Table 21:
Terminal cross sections and earth connection tightening torques
Tightening torquesTerminal cross sectionsConductor type
3 4 Nm2.5 mm² to 6 mm²Solid wire and stranded
3 4 Nm1.5 mm² to 4 mm²Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
36
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive HART

Table of Contents

Other manuals for AUMA SAR 07.6

Related product manuals