1. Pull off indicator disc using a spanner as lever if required.
2. Refer to table and check if turns/stroke of the actuator correspond to the setting
of the reduction gearing (stages 1 9).
If the setting is not correct: continue with step 3.
If the setting is correct: continue with step 6.
MS5.2 control unit (1 to 500 turns per stroke)
Gear stageTurns/stroke above to
11.0 1.9
21.9 3.9
33.9 7.8
47.8 15.6
515.6 31.5
631.5 62.5
762.5 125
8125 250
9250 500
MS50.2 control unit (10 to 5,000 turns per stroke)
Gear stageTurns/stroke above to
110.0 19.5
219.5 39.0
339.0 78.0
478 156
5156 315
6315 625
7625 1,250
81,250 2,500
92,500 5,000
3. Loosen screw [1].
4. Set crown wheel [2] to desired level according to table.
5. Tighten screw [1].
6. Place indicator disc on shaft.
7. Set mechanical position indicator.