9.4. Test run
Only perform test run only once all settings previously described have been
performed.
The direction of rotation can be checked at the position indicator if available. (Chapter
<Direction of rotation at mechanical position indicator: check>)
The direction of rotation must be checked at the hollow shaft/stem if no mechanical
position indicator is available. (Chapter <Direction of rotation at hollow shaft/stem:
check>)
9.4.1. Direction of rotation at mechanical position indicator: check
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
Information Switch off before reaching the end position.
1. Move actuator manually to intermediate position or to sufficient distance from
end position.
62
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2 Control unit: electronic (MWG)
Commissioning (basic settings) ACExC 01.2 Non-Intrusive Profinet