17. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates:
EDIT M1210
OPENING
100%
:EDIT C:ESC
EDIT M1211
CLOSING
100%
:EDIT C:ESC
Use and to select between OPENING and CLOSING.
18. Return to status display:
Press C several times until S0 is displayed.
Information The following fault signals are sent if the torque setting performed has been reached
in mid-travel:
Status indication S0: Operation mode OFF/LOCAL = FAULT IND.
Status indication S0/S6: Operation mode REMOTE = FAULT IND.
Status indication S1: TORQUE FAULT (OPEN) or TORQUE FAULT
(CLOSE) (torque fault)
The fault has to be acknowledged before the operation can be resumed.The
acknowledgement is made:
either by an operation command in the opposite direction.
-
For TORQUE FAULT (CLOSE): Operation command in direction OPEN
-
For TORQUE FAULT (OPEN): Operation command in direction CLOSE
or, in case the torque applied is lower than the preset tripping torque:
- via the push button Reset in selector switch position LOCAL.
- or with the reset command via fieldbus.
9.6 Limit switching: set
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SET LIMIT SWITCHES (M10)
CLOSED POSITION (M100)
OPEN POSITION (M101)
Step by step:
1. Set selector switch to position 0 (OFF).
47
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)