Table 13: Description of the fault indications
DescriptionSignal
Actuator can be operated from REMOTE.
READY
Actuator cannot be operated from REMOTE as the selector switch is in position LOCAL
or OFF.
NOT REMOTE
The EMERGENCY operation mode is active.
EMERGENCY MODE
For combination fieldbus/standard interface function:
Operation via parallel interface.
EXTERNAL CONTROLS
The EMERGENCY STOP button has been operated.
EMCY STOP ACTIVE
Actuator locked (only set for special applications e.g. for by-pass function).
ACTUATOR LOCKED
10.3 Fuses
10.3.1 Fuses within the actuator controls
Fuses F1 and F2 can be accessed after removing the cover [1] on the rear side.
Fuses F3, F4, and F5 are located on the power supply unit and can be accessed
after removing the electrical connection [2].
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
Figure 54: Access to fuses
[1] Rear cover
[2] Electrical connection
F1/F2
Primary fuses on power supply unit
AUMA Art. No.:F1/F2G fuses
6.3 x 32 mmSize
K002.2771 A T; 500 VReversing contactors
Power supply 500 V
K002.6652 A FF; 660 VReversing contactors
Power supply > 500 V
K001.18516 A FF; 500 VThyristor units for motor power up to 1.5 kW
K006.96530 A FF; 500 VThyristor units for motor power up to 3.0 kW
K002.2771 A T; 500 VThyristor units for motor power up to 5.5 kW
F3
Internal 24 V DC supply
F4
Internal 24 V AC supply (115 V AC) for:
Heater, switch compartment, reversing contactors control
PTC tripping device
61
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Corrective action