Select parameter
3. Select parameter either:
click via the menu to parameter, or
via direct display: press and enter ID M0088.
Display indicates: Trip torque CLOSE
CLOSE or OPEN
4.
Use Up Down to select:
Trip torque CLOSE
Trip torque OPEN
The black triangle indicates the current selection.
5.
Press Ok.
Display shows the set value.
The bottom row indicates: Edit Esc
6.
Press Edit.
Display indicates:
-
Specialist (4) continue with step 7
-
in bottom row Up Down Esc continue with step 11
User login
7.
Use Up Down to select user:
Information: Required user level: Specialist (4) or higher.
The symbols have the following meanings:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
8.
Press Ok.
Display indicates: Password 0***
9.
Enter password ( enter password).
Display shows the set value.
The bottom row indicates: Edit Esc
10.
Press Edit.
Change value
11.
Enter new value for tripping torque via Up Down .
Information: The adjustable torque range is shown in round brackets.
12.
Save new value via Save.
The tripping torque is set.
13.
Back to step 4 (CLOSED or OPEN): Press Esc.
Information
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
In the display of the local controls: Status indication S0007 Fault =
Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed.The
acknowledgement is made:
1. either by an operation command in the opposite direction.
-
For Torque fault OPEN: Operation command in direction CLOSE
-
For Torque fault CLOSE: Operation command in direction OPEN
2. or, in case the torque applied is lower than the preset tripping torque:
- in selector switch position Local control (LOCAL) via push button RESET.
- in selector switch position Remote control (REMOTE):
- via a digital (I/O interface) with the Reset command if a digital input
is configured for RESET signal.
50
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.2 Non-Intrusive