Rudolf R2 User's Manual
3BConfiguration Sections - 11BSwitch • 23
4.2 Switch
Alt+W
The switch tab is displayed below, together with all the possible
In the picture below, channel 1 is selected. Channel 1 uses
terminal 7 on the wire terminal card RK-66 R2.
Clicking anywhere on that line will select channel 1. Then click
Active to enable it and complete the fields.
Above, channel 1 is selected. The normally open switch is
connected between terminal 7 and 0V.
Here, the alarm text “LOP Low, Shut Down” will appear
two seconds after the switch opens.
This channel is excluded when the engine is at standstill,
and comes into operation 15 seconds after the engine has
started.
Further, this channel indicates that the engine is running –
together with the rpm.
The terminal number where
the wires are connected