Setting Explanations for Parameters P3.11 through P3.14
Setting 00: AC Drive Running — The terminal will be activated when there is an
output from the drive.
Setting 01: AC Drive Fault — The terminal will be activated when one of the faults
listed under parameters P6.31 through P6.36 occurs.
Setting 02: At Speed — The terminal will be activated when the AC drive attains the
Command Frequency (P4.00).
Setting 03: Zero Speed — The output will be activated when Command Frequency
(P4.00) is lower than the Minimum Output Frequency (P2.06).
Setting 04: Above Desired Frequency — The output will be activated when the AC
drive is above the Desired Frequency (P3.16).
Setting 05: Below Desired Frequency — The output will be activated when the AC
drive is below the Desired Frequency (P3.16).
Setting 06: At Maximum Speed — The output will be activated when the AC drive
reaches Motor Maximum RPM (P0.04).
Setting 07: Over Torque Detected — The output will be activated when the AC
drive reaches the Over-torque Detection Level (P6.08) and exceeds this
level for a time greater than the Over-torque Detection Time (P6.09).
Setting 08: Above Desired Current — The output will be activated when the AC drive
is above the Desired Current (P3.17).
Setting 09: Below Desired Current — The output will be activated when the AC drive
is below the Desired Current (P3.17).
Setting 10: PID Deviation Alarm — The output will be activated when the AC
drive exceeds the PID Deviation Level (P3.18) for longer than the PID
Deviation Time (P3.19).
Setting 11: Heatsink Overheat Warning (OH) — The output will be activated when
the heatsink overheats.The function will be activated as follows:
Temperature range: 1 ~ 15HP, >90°C (194°F) ON; <90°C (194°F) OFF.
Above 15HP: >80°C (176°F) ON; <80°C (176°F) OFF
Setting 12: Soft Braking Signal — If DC Bus voltage is greater than the braking
voltage level set in parameter P6.18 (Braking Voltage level), then any
output configured for function 12 will change state.
Setting 13: Above Desired Frequency 2 — The output will be activated when the
AC drive is above the Desired Frequency.(P3.20)
Setting 14: Below Desired Frequency — The output will be activated when the AC
drive is below the Desired Frequency. (P3.20)
Setting 15: Encoder Loss — The output will be activated when the AC drive
experiences loss of the encoder signal.
Setting *16: PID Feedback Loss Warning — The output will be activated when the
AC drive experiences loss of a 4 to 20 mA PID Feedback signal.
* - Parameter setting available only with firmware v1.04 or higher (refer to P9.39)
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013