Chapter 4: AC Drive Parameters
4–10
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Protection Parameters (continued)
P6.15
Upper Bound of
Output Frequency
0.1 to 400 Hz 400
P6.16
Lower Bound of
Output Frequency
0.0 to 400 Hz 0.0
P6.17
Over-Voltage Stall Prevention
Level
230V series - 330.0V to 450.0V
460V series - 600.0V to 900.0V
390.0
780.0
P6.18
Braking Voltage Level
230V series - 370.0V to 450.0V
460V series - 740.0V to 900.0V
380.0
760.0
P6.30
Line Start Lockout
00: Enable Line Start Lockout
01: Disable Line Start Lockout
00
P6.31
Present Fault Record
00: No Fault occurred
01: Over-current (oc)
02: Over-voltage (ov)
03: Over-temperature
04: Overload (oL)
05: Thermal Overload (oL1)
06: Over-Torque (oL2)
07: External Fault (EF)
08: CPU failure 1 (CF1)
09: CPU failure 2 (CF2)
10: CPU failure 3 (CF3)
11: Hardware Protection Failure (HPF)
12: Over-current during accel (OCA)
13: Over-current during decel (OCd)
14: Over-current during steady state (OCn)
15:Ground fault or fuse failure (GFF)
17: Input power 3-phase loss
19: Auto Ramp Fault
20: Parameters Locked
21: PID Feedback loss (FbE)
22: Encoder Feedback Loss
23: Output Shorted (OCC)
24: Momentary Power Loss
00
P6.32
Second Most Recent Fault
Record
00
P6.33
Third Most Recent Fault
Record
00
P6.34
Fourth Most Recent Fault
Record
00
P6.35
Fifth Most Recent Fault Record 00
P6.36
Sixth Most Recent Fault
Record
00
P6.37
Hunting Gain 0 to 1000 0
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Parameter can be set during RUN Mode.
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013