4–11
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
PID Parameters
P7.00
Input Terminal
for PID Feedback
00: Inhibit PID operation
01: Forward-acting (heating loop) PID
feedback, PV from AI1 (0 to + 10V)
02: Forward-acting (heating loop) PID
feedback, PV from AI2 (4 to 20 mA)
03: Reverse-acting (cooling loop) PID
feedback, PV from AI1 (0 to +10V)
04: Reverse-acting (cooling loop) PID
feedback, PV from AI2 (4 to 20 mA)
00
P7.01
PV 100% Value 0.0 to 999 100.0
P7.02
PID Setpoint Source
00: Keypad
01: Serial Communications
02: AI1 (0 to +10V)
03: AI2 (4 to 20mA)
02
P7.03
PID Feedback Gain 00 to 300.0% 100
P7.04
PID Setpoint Offset Polarity
00: No Offset
01: Positive Offset
02: Negative Offset
00
P7.05
PID Setpoint Offset 0.0 to 100.0% 0.0
P7.06
PID Setpoint Gain 0.0 to 300.0% 100
P7.10
Keypad PID Setpoint 0.0 to 999 0.0
P7.11
PID Multi-setpoint 1 0.0 to 999 0.0
P7.12
PID Multi-setpoint 2 0.0 to 999 0.0
P7.13
PID Multi-setpoint 3 0.0 to 999 0.0
P7.14
PID Multi-setpoint 4 0.0 to 999 0.0
P7.15
PID Multi-setpoint 5 0.0 to 999 0.0
P7.16
PID Multi-setpoint 6 0.0 to 999 0.0
P7.17
PID Multi-setpoint 7 0.0 to 999 0.0
P7.20
Proportional Control 0.0 to 10.0 1.0
P7.21
Integral Control 0.00 to 100.0 sec 1.00
P7.22
Derivative Control 0.00 to 1.00 sec 0.00
P7.23
Upper Bound for Integral Control 00 to 100% 100
P7.24
Derivative Filter Time Constant 0.0 to 2.5 sec 0.0
P7.25
PID Output Frequency Limit 00 to 110% 100
P7.26
Feedback Signal Detection Time 0.0 to 3600 sec. 60
P7.27
PID Feedback Loss
00: Warn and AC Drive Stop
01: Warn and continue operation
02: Warn and continue at last frequency
03: Warn and continue
at Preset Speed (P7.28)
00
P7.28
PID Feedback Loss Preset Speed 0.0 to 400.0 Hz 0.0
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Parameter can be set during RUN Mode.
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013