4–9
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Protection Parameters
P6.00
Electronic Thermal
Overload Relay
00: Inverter/Vector Duty Motors
01: Fan Cooled Standard Motors
02: Inactive
00
P6.01
Auto Restart after Fault 00 to 10 00
P6.02
Momentary Power Loss
00: Stop operation after momentary power
loss
01: Continue operation after momentary
power loss, speed search from Speed
Reference
02: Continue operation after momentary
power loss, speed search from
Minimum Speed
00
P6.03
Reverse Operation Inhibit
00: Enable Reverse Operation
01: Disable Reverse Operation
00
P6.04
Auto Voltage Regulation
00: AVR enabled
01: AVR disabled
02: AVR disabled during decel
03: AVR disabled during stop
00
P6.05
Over-Voltage Stall Prevention
00: Enable Over-voltage Stall Prevention
01: Disable Over-voltage Stall Prevention
00
P6.06
Auto Adjustable Accel/Decel
00: Linear Accel/Decel
01: Auto Accel, Linear Decel
02: Linear Accel, Auto Decel
03: Auto Accel/Decel
04: Auto Accel/Decel Stall Prevention (limited
by P1.01, P1.02, P1.05 and P1.06)
00
P6.07
Over-Torque Detection Mode
00: Disabled
01: Enabled during constant speed
operation
02: Enabled during acceleration
00
P6.08
Over-Torque Detection Level 30 to 200% 150
P6.09
Over-Torque Detection Time 0.1 to 10.0 0.1
P6.10
Over-Current Stall Prevention
during Acceleration
20 to 200%
00: Disable
150
P6.11
Over-Current Stall Prevention
during Operation
20 to 200% 150
P6.12
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec 2.0
P6.13
Base-Block Time
for Speed Search
0.3 to 5.0 sec 0.5
P6.14
Maximum
Speed Search Current Level
30 to 200% 150
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013