4–61
Over-current Stall Prevention during Acceleration Default Setting: 150
Range: 20 to 200%
A setting of 100% is equal to the Rated Output Current of the drive.
Under certain conditions, the AC drive output current may increase abruptly, and
exceed the value specified by P6.10 This is commonly caused by rapid
acceleration or excessive load on the motor. When this function is enabled, the
AC drive will stop accelerating and maintain a constant output frequency. The AC
drive will only resume acceleration when the current drops below the maximum
value.
Over-current Stall Prevention during Operation Default Setting: 150
Range: 20 to 200%
During steady-state operation with motor load rapidly increasing, the AC drive
output current may exceed the limit specified in P6.11. When this occurs, the
output frequency will decrease to maintain a constant motor speed. The drive will
accelerate to the steady-state output frequency only when the output current
drops below the level specified by P6.11.
Output current
Over-current
detection
level
Output current
tim e
Output
frequency
output
freq
tim e
Over-current Stall Prevention
during Operation
tim e
P 6.10
tim e
Over-current
detection
level
P 6.11
Over-current Stall Prevention
during Acceleration
P6.11
P6.10
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013