4–63
Upper Bound of Output Frequency Default Setting: 400
Range: 0.1 to 400 Hz
• The Upper/Lower Bound of Output Frequency is to prevent operation error and
machine damage.
• This parameter must be equal to or greater than the Lower Bound of Output
Frequency (P6.16).
• If the Upper Bound of Output Frequency is 50Hz and the Maximum Output
Frequency is 60 Hz, then any Command Frequency above 50 Hz will generate a
50 Hz output from the drive.
The Output Frequency is also limited by the Motor Maximum RPM (P0.04).
Lower Bound of Output Frequency Default Setting: 0.0
Range: 0.0 to 400 Hz
• The Upper/Lower Bound of Output Frequency is to prevent operation error and
machine damage.
• This parameter must be equal to or less than the Upper Bound of Output
Frequency (P6.15).
• If the Lower Bound of Output Frequency is 10 Hz, and the Minimum Output
Frequency (P2.06) is set at 1.0 Hz, then any Command Frequency between 1-10
Hz will generate a 10 Hz output from the drive.
• The Upper/Lower Bound of Output Frequency is to prevent operation error and
machine damage.
If the reference frequency is less than 0.5 Hz, then this parameter setting is disabled.
Command Frequency
Maximum Output Frequency
P 6.15
P 6.16
P6.16
P6.15
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013