4–7
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Analog Parameters
P4.00
Source of Frequency
Command
01: Frequency determined by digital keypad
up/down
02: Frequency determined by 0 to +10V
input on AI1 terminal
03: Frequency determined by 4 to 20 mA
input on AI2 terminal
04: Frequency determined by 0 to 20 mA
input on AI2 terminal
05: Frequency determined by RS-485
communication interface
06: Frequency determined by -10V to +10V
input on (AI3) terminal
01
P4.01
Analog Input Offset Polarity
00: No Offset
01: Positive Offset
02: Negative Offset
00
P4.02
Analog Input Offset 0.0 to 100.0% 0.0
P4.03
Analog Input Gain 0.0 to 300.0% 100.0
P4.04
Analog Input
Reverse Motion Enable
00: Forward Motion Only
01: Reverse Motion Enable
00
P4.05
Loss of AI2 Signal
(4-20 mA)
00: Decelerate to 0Hz
01: Stop immediately and display error
code “External Fault”
02: Continue operation by the last
frequency command
00
P4.11
Analog Output Signal
00: Frequency Hz
01: Current A
02: PV
00
P4.12
Analog Output Gain 00 to 200% 100
P4.13
2nd Source of
Frequency Command
same settings as for P4.00 06
P4.14
2nd Analog Input
Offset Polarity
same settings as for P4.01 00
P4.15
2nd Analog Input Offset 0.0 to 100.0%
0.0
(float)
P4.16
2nd Analog Input Gain 0.0 to 300.0%
100.0
(float)
P4.17
Trim Frequency Reference 0.0 to 400.0 Hz 0.0 (float)
P4.18
Trim Mode Select
00: Disable Trim function
01: 1st source frequency + 2nd source freq
02: 1st source frequency - 2nd source freq
03: Speed Command +
Trim Frequency Reference (P4.17)
04: Speed Command -
Trim Frequency Reference (P4.17)
00
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to