9 Communication
© Copyright Reserved Autonics Co., Ltd. 81
9.3 Parameter value read/write via communication
(1) Parameter area for reading available only
000002 (OUT2), 000003 (OUT1), 000004 (BATCH output)
100001 to 100005 (Terminal input status)
300101 to 300125 (Product information)
310001 to 310013 (Monitoring data)
(2) Parameter area for reading/writing available
000001 (RESET), 000005 (BATCH RESET)
400001 to 400006 (Setting value saving group)
400051 to 400066 (Counter group)
400101 to 400110 (Timer group)
400151 to 400156 (Communication group)
(3) Communication reading action
Reads parameter values via communication. (Func: 01 H, 02 H, 03 H, 04 H)
Communication reading is available regardless of communication write [COmW]
enable/disable setting.
(4) Communication writing action
Changes parameter values via communication. (Func: 05 H, 06 H, 16 H)
When changing counter or timer parameters using Func06 H, Func16 H,
communication RESET flashes for 3 sec at the front and RESET starts.
The setting values about counter/timer is changed and RESET starts automatically and
the present value is not saved.
When changing setting value or communication setting parameters using Func06 H,
Func16 H, the action is not reset.
To write action using Func05 H at Modbus RTU protocol, enter 1 as FF00 H.
When 00001 is set as FF00 H using Func05 H, RESET starts immediately.
When 00005 is set as FF00 H using Func05 H, BATCH RESET starts immediately.
When communication write is set as disable(COmW=1), it does not execute write action.
When setting value is out of the range, the dedicated value by operation mode is
replaced and saved.