6 Timer mode
© Copyright Reserved Autonics Co., Ltd. 61
6.2 Parameter setting
( key: moves parameters, key: changes parameter setting value)
Parameter
Parameter setting value
Counter/Timer
[C-T]
COUNT: Counter
TIME: Timer
UP/DOWN mode
[U-D]
UP: Time progresses from '0' to the setting time.
DN: Time progresses from the setting time to '0'.
Output mode
[OUtM]
Time range
3
[tRNG]
Output ON time
range
4
[OnRNG]
,
Output OFF time
range
4
[OFfRNG]
OUT2
output time
5
[OUT2]
Set one-shot output time of OUT2.
Setting range: 00.01 to 99.99 sec, HOLD
When number of tens digit is flashing, press the key once and HOLD
appears.
OUT1
output time
5
[OUT1]
Set one-shot output time of OUT1.
Setting range: 00.01 to 99.99 sec, HOLD
When number of tens digit is flashing, press the key once and HOLD
appears.
OUT output time
5
[OUtT]
Setting range: 00.01 to 99.99 sec, HOLD
When number of tens digit is flashing, press the key once and HOLD
appears.
Input logic
6
[SIG]
NPN: No-voltage input, PNP: Voltage input
Input signal time
6
[IN-T]
, unit: ms
Set min. width of INA, INHIBIT, RESET, TOTAL RESET signal.
Memory protection
[DATA]
CLR: Resets the counting value when power OFF.
REC: Maintains the counting value when power OFF. (memory protection)
Key lock
[LOCK]
lOFF: Unlock keys, key lock indicator OFF
LOc1: Locks key, key lock indicator ON
LOc2: Locks , keys, key lock indicator ON
LOc3: Locks
, , keys, key lock indicator ON