Alarm
Set both alarm operation and alarm option by combining. Each alarm operates individually in two alarm output models. When the
current temperature is out of alarm range, alarm clears automatically. If alarm option is alarm latch or alarm latch and standby
sequence 1/2, press digital input key( + 3 sec, digital input key[DI-K] of parameter 2 group set as AlRE), or turn OFF the power and
turn ON to clear alarm.
Mode Name Alarm operation Description
A )_ No alarm output
A !
Deviation high-limit
alarm
OFF H ON SV PV
100110 High-limit
deviation: Set as 10
OFF H ON PV SV 90
100 High-limit deviation: Set
as -10
If deviation between PV and SV as
high-limit is higher than set value of
deviation temperature, the alarm
output will be ON.
A @
Deviation low-limit
alarm
ON H OFF PV SV
90 100 Low-limit
deviation: Set a 10
ON H OFFSV
PV100 110 Low-limit
deviation: Set as -10
If deviation between PV and SV as
low-limit is higher than set value of
deviation temperature, the alarm
output will be ON.
A #
Deviation high/low-
limit alarm
ON H OFF H ON
PV SV PV
90 100 110 High, Low-limit deviation:
Set as 10
If deviation between PV and SV as
high/low-limit is higher than set
value of deviation temperature, the
alarm output will be ON.
A $
Deviation high/low-
limit reserve alarm
OFF H ON H OFF PV
SV PV 90 100 110 High,
Low-limit deviation: Set as 10
If deviation between PV and SV as
high/low-limit is higher than set
value of deviation temperature, the
alarm output will be OFF.