EasyManua.ls Logo

Avocent Cyclades ACS 5000 - Page 113

Avocent Cyclades ACS 5000
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6: Power Management 105
Wake Up State
(SPC and
ServerTech)
wakeup
<outlet list> [on | off | last]
Set the outlet state after a cold boot. It can be set to On,
Off or the last saved state.
[last] is for ServerTech only.
Sequence Interval seqinterval
<outlet list> [<interval>]
Set the delay time (in seconds) when turning on multiple
outlets at the same time (Valid only on a master Server
Technology Sentry CDU).
Cycle Interval
(ServerTech)
cycleinterval
<outlet list> [<interval>]
Set the time delay (in seconds) for turning on
subsequent outlets after an outlet has been turned on.
(N/A) menu Enter menu mode (from pmCommand only).
Cold Start Delay
(Avocent PM
PDU)
coldstartdelay <IPDU ID>
<duration>
Set the duration of the cold start delay for the defined
PDU or all connected PDUs when one is not defined.
Current Threshold currentthreshold <IPDU ID>
[<element>] <thresholds>]
Display or set the threshold for current of one element
Set command requires <element> argument.
The <element> can be pdu, bank name (A, B, C, XY, ...),
phase name (X, Y, Z), outlet number (1, 2, ... )
Power Off Delay
(Avocent PM
PDU)
poweroffdelay <outlet list>
<delay>
Set the time delay (in seconds) for turning off outlets.
Power Info powerinfo [reset] [<IPDU
ID>] [<element>]]
Display or clear the maximum/minimum/average power
consumption of a defined element or all elements if one
is not defined.
The <element> can be bank name (A, B, C, XY, ...),
phase name (X, Y, Z), outlet number (1, 2, ..)
Cumulative Power cumulativepower [reset]
[<IPDU ID> [<element>]]
Display or clear the cumulative power consumption of a
defined element, or all elements if one is not defined, to
zero.
The <element> can be bank name (A, B, C, XY, ...),
phase name (X, Y, Z), outlet number (1, 2, ..)
Power Factor powerfactor [reset] [<IPDU
ID> [<element>]]
Display or reset the maximum/minimum/average
recorded power factor of a defined element or all
elements if one is not defined.
The <element> can be bank name (A, B, C, XY, ...),
phase name (X, Y, Z), outlet number (1, 2, ...)
Table 6.1: pmMenu and pmCommand Commands (Continued)
Menu Item Command Syntax Description

Table of Contents

Other manuals for Avocent Cyclades ACS 5000

Related product manuals