Key Introduce Operation Manual
Key Function 1.In normal display,The key function is call out setting group
2.In parameter setting page,The key function is data Enter , and goto next page
Key Function 1.In normal display,The key function is call out alarm value setting page
2.Into parameter setting page,the parameter mark&data is alternate display,If need modify data can
press shift key into setting procedure,The display is lock parameter data,this time must let off key
about 0.2 sec,press again,the cursor(twinkle express)is cycle moving left.
sec)
Key Function 1.In normal display,The key function is call out adjustment display value (DZERO&DSPAN)page
2.Into parameter setting page,the parameter mark&data is alternate display,If need modify data can
press up key into setting procedure,The display is lock parameter data,this time must let off key
about 0.2 sec,press again,the parameter data will increment. (Key Response about 0.2 sec)
Key Function 1.In normal display,The key function is call out adjustment analog output (AZERO&ASPAN)page
ameter setting page,the parameter mark&data is alternate display,If need modify data can
press down key into setting procedure,The display is lock parameter data,this time must let off key
about 0.2 sec,press again the parameter data will decrement. (Key Response about 0.2 sec)
&
Key Function In setting group or setting page press
&
key return normal display,but if in setting page the
modify data will be lost
No Key in anything In setting group or setting page no key in anything about 2 minutes,return normal display
Step Parameter Mark Description
Operation Manual
1
Normal display
Press
/FUNC key into P.COD setting page
2
P.COD(Pass code input
page)
1.Key in 5 digit pass code with
or
or
key
2.Press
key,the pass code is right into setting grou
otherwise
return normal display
3 SYS(System setting group)
AOP(Analog output setting
DOP(Communication
setting group)
1.
Select setting group with
key
2.
Press
key into setting page of selection setting group
4
SYS(System setting group)
Press
key decide SYS setting group , press
DP(Decimal Point)
Default=0
1. Decide decimal point position with
or
key (0 to 4)
2. Press
key enter data and into DSPL setting page
1.Decide display low scale with
&
&
key (-19999~19999)
2.Press
key enter data and into DSPH setting page
1.Decide display high scale with
&
&
key (-19999~19999)
2.Press
key enter data and into AVG setting page
AVG (Average)
Default=1
1.Decide display Average times with
&
&
key (1~99)
2.Press
key enter data and into LCUT setting page
LCUT (Low Cut)
Default=0
1.Decide display low cut with
&
&
key (0~99)
2.Press
key enter data and into CODE setting page
CODE(Pass Code)
Default=0
1.Decide Pass code with
&
&
key (0~19999)
2.Press
key enter data and into LOCK setting page
LOCK(Panel Lock)
Default=NO
1.Decide panel lock with
or
key (NO or YES)
2.Press
key enter data and return SYS setting group
5
ROP(Alarm setting group)
Press
key decide ROP setting group,press
key into
ACT1 setting page
ACT1(Alarm Active 1
setting page )Default=HI
1.Decide active 1 with
or
key(HI or LO)
2.Press
key enter data and into ACT2 setting page
ACT2(Alarm Active 2
setting page )Default=HI
1.Decide active 2 with
or
key(HI or LO)
2.Press
key enter data and into ACT3 setting page