Azbil Corporation Electrical wiring
Model MTG11A/18A, MTG11B/18B, MTG14C 3-9
Wiring procedure
Carry out the wiring between the instrument and a power supply must be done
according to the following procedure.
*: The numerical value in parentheses is a reference value.
Step Procedure
1 The terminal box cover is fixed by hexagon socket head setscrews (M3).
Loosen the setscrews with an Allen wrench (1.5).
2 Remove the terminal box cover by turning it counterclockwise with the
dedicated tool.
3 Remove the dust plug from the socket for an output signal line conduit.
4 Insert the cable into the conduit cable ground.
~Note • Take care not to damage the cable sheath.
5 Referring to Figure 3-6, connect the cable to the output signal terminals
(IOUT+, -) of the terminal box.
~Note • Pay attention to the polarity.
• Tighten the terminal screws adequately. The
recommended tightening torque is 1.1 ft·lb (1.5 N·m)*.
6
Waterproof the conduit sufficiently to prevent ingression of rainwater, etc.
~Note • We recommend using a silicon resin-based non-curing
sealant.
7 Attach the terminal box cover and tighten it adequately with the
dedicated tool. Then, fix the cover with the setscrews.
~Note • Take care not injure your fingers on the cover edge or the
carrying thread.
CM2-MTG300-2001.book 9 ページ 2015年9月29日 火曜日 午前10時14分