EasyManua.ls Logo

Azbil Neostat HY9000Z - Page 4

Azbil Neostat HY9000Z
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AB-7259
4
Specifications
Item Specification
Proportional bands Approx. 12 %RH fixed (at 50 %RH)
Sensing element Nylon ribbon
Power supply 24 V AC -15/+10 % (50 Hz/60 Hz)
Environmental conditions Rated operating conditions Transport/storage conditions
Ambient temperature 15 °C to 40 °C -20 °C to 50 °C
Ambient humidity 10 %RH to 95 %RH (non-condensing) Max. 95 %RH (non-condensing)
Color Pale gray
Cover PC resin Materials
Base Modified PPE resin
Weight Approx. 190 g
Installation With the optional mounting kit (sold separately)
Connection Lead wire connection
Accessory Four mounting screws (M3 x 16)
PPE: Polyphenylene ether
Dimensions
Neostat with Wall-direct mounting kit
Note:
* Secure more than 15 mm clearance inside the mounting wall when installing Neostat with Wall-direct mounting kit.
Figure 1. Mounting dimensions (mm): Neostat with Wall-direct mounting kit
Mounting plate
Note:
* Use JIS outlet box/box cover (JIS C8340:1999) with 66.7 mm mounting dimension.
JIS: Japanese Industrial Standards
Figure 2. Dimensions (mm): Mounting plate of Wall-direct mounting kit
Connectors for connection check
Wall-direct
mounting kit
90
77
77
90
77
38.5
16.5
15*
Mounting
surface
Heat sink
77
80
66.7*
80
Mounting screw (M3)
4.2 mounting hole
Mounting hole
4.2