www.balluff.com 13english
The module must be integrated into the control system.
The corresponding IODD file is used for this.
The IODD can be downloaded free of charge from
www.balluff.com.
The section below describes parameters for the necessary
configuration of the digital hub.
7.1 Process data profile
PDInput (2bytes)
Byte0 Byte1
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Input
Port7–Pin4
Input
Port6–Pin4
Input
Port5–Pin4
Input
Port4–Pin4
Input
Port3–Pin4
Input
Port2–Pin4
Input
Port1–Pin4
Input
Port0–Pin4
Input
Port7–Pin2
Input
Port6–Pin2
Input
Port5–Pin2
Input
Port4–Pin2
Input
Port3–Pin2
Input
Port2–Pin2
Input
Port1–Pin2
Input
Port0–Pin2
7.2 IO-Link Parameters
7.2.1 Identification data – DPP
Name Index Access Length Data
Type
Data
Storage
Default
Vendor Name 0x0007 (7) R 2bytes STRING n/a 0x0378
Vendor text 0x0008 (8) R STRING n/a
Product Name 0x0009 (9) R 3bytes STRING n/a 0x050112
Product ID 0x000A (10) R STRING n/a
Product text 0x000B (11) R STRING n/a
Tab. 7-1: Identification data – DPP
7.2.2 Identification data – ISDU
Name Index Subin-
dex
Access Length Data
Type
Data
Storage
Default
Vendor Name 0x0010 (16) 0 R 7bytes STRING n/a Balluff
Vendor text 0x0011 (17) 0 R 15bytes STRING n/a www.balluff.com
Product Name 0x0012 (18) 0 R […] STRING n/a BNI IOL-104-
011-K006
Product ID 0x0013 (19) 0 R […] STRING n/a BNI00J0
Product text 0x0014 (20) 0 R […] STRING n/a Sensor Hub M12
Serial Number 0x0015 (21) 0 R 16bytes STRING n/a
Hardware Revision 0x0016 (22) 0 R 2bytes STRING n/a
Firmware Revision 0x0017 (23) 0 R ≤10bytes STRING n/a
Application Specific Tag 0x0018 (24) 0 R/W ≤32bytes STRING Yes „***“
Tab. 7-2: Identification data – ISDU
7
IO-Link Configuration
BNI IOL-104-011-K006
Network interface – Digital hub

Table of Contents

Related product manuals