www.balluff.com 13english
The module must be integrated into the control system.
The corresponding IODD file is used for this.
The IODD can be downloaded free of charge from
www.balluff.com.
The section below describes parameters for the necessary
configuration of the digital hub.
7.1 Process data profile
PDInput (2bytes)
Byte0 Byte1
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Input
Port7–Pin4
Input
Port6–Pin4
Input
Port5–Pin4
Input
Port4–Pin4
Input
Port3–Pin4
Input
Port2–Pin4
Input
Port1–Pin4
Input
Port0–Pin4
Input
Port7–Pin2
Input
Port6–Pin2
Input
Port5–Pin2
Input
Port4–Pin2
Input
Port3–Pin2
Input
Port2–Pin2
Input
Port1–Pin2
Input
Port0–Pin2
7.2 IO-Link Parameters
7.2.1 Identification data – DPP
Name Index Access Length Data
Type
Data
Storage
Default
Vendor Name 0x0007 (7) R 2bytes STRING n/a 0x0378
Vendor text 0x0008 (8) R STRING n/a
Product Name 0x0009 (9) R 3bytes STRING n/a 0x050112
Product ID 0x000A (10) R STRING n/a
Product text 0x000B (11) R STRING n/a
Tab. 7-1: Identification data – DPP
7.2.2 Identification data – ISDU
Name Index Subin-
dex
Access Length Data
Type
Data
Storage
Default
Vendor Name 0x0010 (16) 0 R 7bytes STRING n/a Balluff
Vendor text 0x0011 (17) 0 R 15bytes STRING n/a www.balluff.com
Product Name 0x0012 (18) 0 R […] STRING n/a BNI IOL-104-
011-K006
Product ID 0x0013 (19) 0 R […] STRING n/a BNI00J0
Product text 0x0014 (20) 0 R […] STRING n/a Sensor Hub M12
Serial Number 0x0015 (21) 0 R 16bytes STRING n/a
Hardware Revision 0x0016 (22) 0 R 2bytes STRING n/a
Firmware Revision 0x0017 (23) 0 R ≤10bytes STRING n/a
Application Specific Tag 0x0018 (24) 0 R/W ≤32bytes STRING Yes „***“
Tab. 7-2: Identification data – ISDU
7
IO-Link Configuration
BNI IOL-104-011-K006
Network interface – Digital hub