6 Configuration: extended with BNI IOL-102-002-Z019
Safe state of
Outputs 42
hex
The safe state parameter makes it possible to configure the outputs in case of a fault. If no IO-
Link communication is possible or the "valid flag" of the output process data has not been set
by the master, then each output adopts the configured status. The following statuses can be
configured for each pin.
Safe state of
the outputs on
Pin 4 42
hex
Byte
0
1
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Sub-
index
4 3 2 1 8 7 6 5
Description
Safe state Port 3 Pin 4
Safe state Port 2 Pin 4
Safe state Port 1 Pin 4
Safe state
Port 0 Pin 4
-
Safe state Port 6 Pin 4
Safe state Port 5 Pin 4
Safe state Port 4 Pin 4
Value
Output state
bin
dec
00
0 Output is 0V
01
1 Output is 24V
10
2
Current status is maintained
11
3 Not permitted