3 Getting Started
Example 2:
The analog mode is set to 4-20 mA
The resolution is 12 bit.
The process data is left aligned.
The digitalized value read over IO-Link is ABC0
hex
In case of 4-20 mA, the analog input current range is between 3.8 mA and 20.5 mA. The
digitalized value is read over IO-Link as a 16 bit value, but the resolution is 12 bit and it is
left aligned, so the 12 bit digitalized data is ABC
hex
= 2748.

󰇟

󰇠





 

 
Example 3:
The analog mode is set to TypJ Thermocouple.
The resolution is 16 bit
The digitalized value read over IO-Link is 4567hex = 17767

󰇟

󰇠








󰇛

󰇜


󰇛

󰇜
