3 Getting Started
Example 3:
The analog mode is set to 4-20 mA
The digitalized value read over IO-Link is 3A9F
hex
= 15007.
In case of current input, the dimensioned value has the dimension of uA.

󰇟

󰇠





Example 4:
The analog mode is set to TypJ Thermocouple.
The digitalized value read over IO-Link is 06F1hex = 1777
In case of Thermocouple input, the dimensioned value has the dimension of 0.1 °C

󰇟

󰇠




