Pin 1 SC, Wire break Port 7
Pin 1 SC, Wire break Port 6
Pin 1 SC, Wire break Port 5
Pin 1 SC, Wire break Port 4
Pin 1 SC, Wire break Port 3
Pin 1 SC, Wire break Port 2
Pin 1 SC, Wire break Port 1
Pin 1 SC, Wire break Port 0
Pin1 SC, Wire break bit: This bit indicates a short circuit condition of the sensor supply in case of
voltage or current input, or wire break condition in case of Pt100, Pt1000, Typ J or Typ K sensors
on the corresponding port.
Underflow bit: This bit indicates when the measured signal is lower than the selected range.
Overflow bit: This bit indicates when the measured signal is higher than the selected range.
4.3. Process
data /
Output data
When an input port is configured as a voltage or current input, +24V voltage will be switched
between pin1 and pin3 of the input port. This supply voltage is short circuit protected. The supply
voltage will be switched off in case of short circuit, in order to reduce the power dissipation. The
short circuit error is latched and it can be reset with a 0 -> 1 transition on the corresponding bit in
the output process data.