Thermo-
couple
grounding
F9
hex
There are three types of thermocouples: ungrounded, grounded and exposed. The BNI IOL-719-
002-Z012 is able to measure all of them, but in case of grounded thermocouple the
measurement range is reduced. The thermocouple type must be set in the ISDU in order to
measure the thermocouples correct.
0 = Ungrounded thermocouple
1 = Grounded thermocouple
Subindex 0:
The ungrounded measurement mode should be selected in case of ungrounded and in case of
exposed thermocouple. In case of exposed thermocouple the hot junction must not have
galvanic connection to conductive surfaces.
In case of grounded thermocouple the sheath of the thermocouple must be connected to the
ground.
Parameter Value out of Range
Parameter length underrun
Short circuit on pin1 (on at least one of the ports)
Measurement value is out of range
Wire break detected on some port
Short circuit on pin1 (on at least one of the ports)
Measurement value is out of range
Wire break detected on some port