13
4 The Easy Tool-ID System
4.9. Troubleshooting
System does not respond:
• Verify that the data carrier is positioned correctly in front of the read/write head.
• Verify that the system is correctly connected to the equipment.
• Verify that a configuration is installed on the microcontroller. (See status indicator.)
• If necessary, perform a reset. (Disconnect the system from the power and the USB port
from the HMI, wait a minute and then reconnect them.)
The system does not output the data in the correct sequence or outputs the wrong data:
• Check whether the configuration was prepared according to the specifications
• Verify that the data were correctly written on the RFID data carrier
• Reinstall the configuration if necessary
Note
If none of the aforementioned measures remedies the error, Balluff Service will be
happy to help you. https://www.balluff.com/local/de/support/