remarks regardIng fIrst IgnItIon
After rst ignition or after any maintenance work, carry out the following safety checks:
Safety checks Expected result
Burner start with previously interrupted ame detector line
Lock-out cannot be modied at the end of the safety time
Burner operation with ame loss simulation. To this end, interrupt the fuel supply
Lock-out cannot be modied
Burner operation with air pressure drop simulation
Lock-out cannot be modied
After each non-modiable lock-out, the red light comes on.
IMPORTANT
To identify the error code, please refer to the section “Faulty Operation - causes - solutions”.