© Banner Engineering Corp. www.bannerengineering.com 24
PROFINET
®
6.3.1. Save and Upload the Configuration File
After making any changes to the configuration, you must save the configuration files to your computer, then upload it to the device.
CONTEXT:
Changes to the XML file are not automatically saved. Save your configuration file before exiting the tool and before sending the XML file to the
device to avoid losing data. If you select DXM > Send XML Configuration to DXM before saving the configuration file, the software will prompt
you to choose between saving the file or continuing without saving the file.
1. Save the XML configuration file to your hard drive by going to the File > Save As menu.
2. Go to the DXM > Send XML Configuration to DXM menu.
Figure 1: Status indicator bar
• If the Application Status indicator is red, close and restart the DXM Configuration Tool, unplug and re-plug in the cable and recon-
nect the DXM to the software.
• If the Application Status indicator is green, the file upload is complete.
• If the Application Status indicator is gray and the green status bar is in motion, the file transfer is in progress.
S
TEP RESULT: After the file transfer is complete, the device reboots and begins running the new configuration.
6.4. Slots and Modules for DXM PROFINET
There are ten slots to accommodate the DXM Controller data.
It is important to note that the module placed in slot 2 corresponds to Port 1; the module placed in slot 3 corresponds to Port 2; the module placed
in slot 4 corresponds to port 3. etc.
For the DXMR90-4K IO-Link Master device, slots 6 through 9 are unused.
If the IO-Link In/Out process data modules (all except digital input and output) are used, the attached IO-Link device must have PDI and PDO
size less than or equal to the number of data bytes allowed in the module. Data transfers will not be applied otherwise. For example,
plugging in the 16/16 byte module to a slot corresponding to a device that has 22 bytes of PDO results in an error. Process data sent from the
PLC to DXM will not be applied.
Table 1: Slots for input and output values
Values Maximum Data Size
Input values 1440 bytes
Output values 1440 bytes
Table 2: Slot 1 - Input (DXM --> PLC)
Module ID Submodule ID Module Size (bytes) Register Start Register End Direction
0x44 0x01
Banner IO-Link
Master Info
9
1 3
Input6 6
123 123
Table 3: Slots 2-9 (1 per IO-link port) (Sheet 1 of 2)
Module ID Submodule ID Module Size (bytes) Register Start Register End Direction
0x45 0x01
IO-Link In/Out
32/32 Byte + Status
36
x001 x017
Bidirectional
x506 x507
46
x051 x067
x851 x859
0x46 0x01
IO-Link In/Out
16/16 Byte + Status
20
x001 x009
Bidirectional
x506 x507
30
x051 x059
x851 x859