June 11, 2009 Page 73
This electrical panel will power up to a single 50 HP NEMA Design B motor at 460 VAC. The panel is
provided with a 120 VAC, 200 VA, single-phase transformer for powering 120-volt loads. 120 VAC
single-phase panel loads are as follows:
AC Power Available Light Negligible
Warning & Alarm lights Negligible
ACD coils (up to 4) 35 W each maximum, with 3 max energized
Motor Starter coil (max) 26.0 VA (sealed, max)
CO Monitor Solenoid valve 8 W
CO Monitor power 0.9 W
Securus
®
Electronic Moisture Monitor System 20.4 VA
PLC Controller 22.0 VA
Figure 7-2 Electrical Panel Label
Figure 7-3 Transformer and Fuses