7.7.1 Installing a new program using an EEPROM cartridge
1. Disconnect main power to your unit
2. Open the electrical enclosure door
3. Open the bottom terminal cover on the Twido controller
4. Remove the cartridge cover
5. Push the EEPROM cartridge into the cartridge connector until it “clicks”.
6. Close the terminal cover.
7. Reconnect main power to the unit.
8. Pull out the Emergency Stop pushbutton.
9. At power up, the new program will automatically be downloaded to the Twido controller. When the
red error light on the front of the Twido controller stops blinking, the download is complete.
10. Disconnect main power to your unit
11. Remove the EEPROM cartridge
12. Replace the cartridge cover
Figure 7-14 PLC EEPROM
^ CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or mod-
erate injury. It may also be used to alert against unsafe practices.
EEPROM Cartridge
PLC with cartridge removed. PLC with EEPROM Installed