T 8 Error detetion and trouble sho oting
Error
no.
Mea ning Reaction Troubleshooting
43 Parameter cannot be changed because
of operational status
— Check operating status and
parameterization
44 Invalid parameter value — Enter a valid value.
45 WinBASS is not connected anymore or
is inactive (Timeout is adjustable)
ad-
justable
Establish connection again or set
parameter P0290 to 0.
46–47 Not assigned — —
48 Error in function module A — See error in the function module A
P0240
• ExtendedModuleError (Error in the module Extension) P0204
Error
no.
Mea ning Reaction Troubleshooting
49–52 Not assigned — —
53 CANopen error at node-guarding ad-
justable
Check the CAN-bus (configuration,
master, nodeguarding)
54–63 Not assigned — —
64 Mains input failure PI Re-establish the connection to the
mains input again.