T 11 Setting out of operation, storage
11.5 Storage onditions
The device is maintenance-free. If you keep to the environmental conditions during the entire per iod of
storage, you can assume, that the device will not be damaged. In case the environmental conditions during
storage are not kept, you should assume that the device is damaged after storage.
CAUTION
The following can occur, if you disregard this warning instruction:
• Damage to property
The danger is: envir o nmental conditions. Wrong storage can damage/destroy the devic e.
Assure, that the environmental conditions are kept during the entire period of storage:
• Climatic category: 1 K 4
• Temperature range: -30°C to +70°C
11.6 Reommissioning
Execute commissiong as with a new device, see «Mounting» from page 43 «Installation» from page 53 and
«Operation» from page 111.
CAUTION
The following can occur, if you disregard this warning instruction:
• Damage to property
The danger is: recommissioning, without forming of the capacitors. From a six month storage
period on, the capacitors are destroyed during comm is sioning, if they are not reformed before-
hand.
• For m the capacitors by supplying the device ready-to-operate for at least one hour with
supply voltage, but do not transmit a pulse enable during this time.
148
Instrution Manual
b maXX
®
BM3400
from 206 Doument No.: 5.07013.03
Baumueller Kamenz GmbH