Measures for EMC assurane 6.8T
ing) can affect the screening effect of the cabinet. Therefore also connect the cab le screens at the exiting
point with a well conductive screening. The distance of the last screen contact point to the cabinet exit
must be as short as possible.
Figure 6.7: Screen layer when exiting the sw itching cabinet
6.8.3 Sreening
The screening of cables is effective with magnetic elds, if it is connected to ground on both ends.
With electrical fields a screening effect is already existent if the screen is connected to ground on one
side.
Figure 6.8: Cable laying with two-sided screening plate
Fields with high frequencies are always electromagnetic fields. Thereby it doesnt matter if it is an elec-
tric or magnetic eld. At these fields the screening always has to be done on both sides. With two-sided
applying of the screen on ground you achieve that the cable doesnt leave the screening „System cabi-
net“.
The two-sided grounding of cable screenings nearly excludes an influence due to ground loops (poten-
tial differences on the ground system).
Instrution Manual
b maXX
®
BM3400
65