Operating sequene of installation 6.10T
6.10 Op erating sequene of installation
WARNING
The following c an occur, if the safety instruction is not complied with:
serious personal injury
d eath
The danger is: electricity. Parts, which are under voltage are extremly dangerous.
Assure, that during the entire mounting the device, the parts, which are to be mounted (e.g.
mains lines) and mounting range are off-circuit.
The following steps must be carried out at installation:
1. Lay all cables EMC-compatible.
2. Connect the cables (see «connection diagrams» from page 72)
Connect the motor via the terminals X204 (1U2, 1V2, 1W2, PE). Attend to the in-phase connection
(rotational direction).
Connect the fuses.
Connect the 24V-supply via the terminals X100 (former X201). (in case you consider UL 508 C:
limit the current to 4A).
Connect the mains via the terminals X202 (1U1, 1V1, 1W1, PE).
Connect encoder.
Connect a signal source for the pulse enable via the terminals X26.
Connect a signal source for the quickstop via the terminals X26.
Connect, if necessary, a jumper at the terminals X205 (Ba- and Bal) for the activation of the inter-
nal chopper resistor.
I f necessary, connect (dependent on the application) a chopper resistor via the terminals X205
(Ba+ and 1C1).
Connect the safety relay (if existent) via X102 (+24V_R and M24V_R).
I f required, connect the motor temperature sensor via X101 (MT+ and MT-) and the brake via
X101.
Instrution Manual
b maXX
®
BM3400
69
Doument No.: 5.07013.03 from 206