Procedure of the commissioning
Instruction handbook b maXX (BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08 Baumüller Nürnberg GmbH
48
of 82
8.2
9 Choose „Input D.1“ in drop down list if the Analog IO module is used in position/slot D.
Figure 13: Analog input link 1
10 Check whether the text: „module not existent“ is displayed directly under the scale.
In this case, the module was not recognized.
Figure 14: Module not existent
m Only if there is no message under the scale, the AIO-XX or BM4-F-AIO-XX is rec-
ognized properly and can be used.
m If the AIO-XX or BM4-F-AIO-XX is not recognized, then switch off the device and
check the assembly/installation. After having removed all errors, restart the device
for checking whether the plug-in module gets recognized properly now.
m If the Analog IO module is not recognized yet, then it is defective or the controller/
controller slot. In that case, contact Baumüller Nürnberg GmbH for replacement.
m Once the Analog IO module has been recognized properly following with
ZTesting of the Analog IO modulefrom page 49.