Procedure of the commissioning
Instruction handbook b maXX (BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08 Baumüller Nürnberg GmbH
50
of 82
8.2
8.2.2.1 Testing of inputs AIO-01, -02 and -03
1 ProDrive Navigation „IO analog inputs“.
2 Select „Analog input link 1“ in ProDrive.
Figure 15: Analog input link 1, AIO-01, -02 and -03
3 By clicking on the g-symbol, select the entry „Input D.1“ („D“ module in position D,
„1“ input 1) from the drop-down list.
Figure 16: Input selection AIO-01, -02 and -03
4 Enter in menu „analog input link 1“:
m Target parameter number: „1171“, (ramp function generator input)
m Smoothing time: „10 ms“,
m Scaling factor: „1“,
m Offset: „0“,
m Threshold: „0“,
A scale is displayed and shows the applied voltage (set by the potentiometer), e. g. +10 V.