BFN 3-1-... -001 0250 0320 0400 0600
Max.
supply voltage
3 x 480 V
AC
+10 %, 50/60 Hz
Rated current
(at T
B
= 50 °C)
250 A 320 A 400 A 600 A
Peak current
(at T
B
= 50 °C)
4 x I
N
at switch-on
1,5 x I
N
for < 1 min / once per hour
Test voltage Cable - Cable: 2150 V
DC
/ 2 s
Cable - Cabinet: 2700 V
DC
/ 2 s
Connection Bolt M10 rail with hole 11mm
PE: Bolt M12
Power loss (typical) 60 W 40 W 50 W 65 W
Protection class IP 00
BFN 3-1-... -101 0320 0400 0600 1000
Max.
supply voltage
3 x 480 V
AC
+10 %, 50/60 Hz
Rated current
(at T
B
= 50 °C)
250 A 320 A 400 A 1000 A
Peak current
(at T
B
= 50 °C)
1,5 x I
N
for < 3 min per hour
or
2,5 x I
N
for 30 s per hour
Test voltage Cable - Cable: 2280 V
DC
/ 2 s
Cable - Cabinet: 2690 V
DC
/ 2 s
Connection Rail with hole 11mm
PE: Bolt M10
Rail with hole
14mm
PE: Bolt M12
Power loss (typical) 31 W 48 W 84 W
Protection class IP 00
Technical Data
Instruction handbook Mains filters BFN
Document No.: 5.09010.03
31
of 70
3