Instruction handbook Mains filters BFN
Document No.: 5.09010.03
49
of 70
7
7.5.2 Measures taken to assure EMC
The following configuration notes must be considered to assure EMC.
Cabling m All conn
ected cables must be screened in order to suppress interfering radiation out-
side the power converter. If the screening atte
nuation of the control cabinet is high
enough (see limit values of the interference emission complying with EMVG for your
system) and if the EMC-compatibility in the internal space is ensured (this can be as-
sumed if the configuration notes of this chapter
are complied with), the control cables
can be mounted unscreened.
Consider the information submitted in ZScreening– on page 52.
Figure 13: Cabling power unit