FR Series
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
FR-98 119,000 120,000 CG4001 CG4MUF3 F3G 1.75" 0.316 0.219 Yes S-8 / B-0 4 - slot
FR-122 154,000 140,000 CG4001 CG4MUF3 F3G 1.75" None 0.242 No S-7 / B-0 4 - slot
HGSI 140,000 140,000 CG4001 CG4MUF3 F3G 1.75" None 0.242 No S-7 / B-0 4 - slot
CL Series
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
CL3-105 105,000 110,000 CG4001 CG4MUF3 F3G 1.75" 0.277 0.206 5880 S-7 / B-0 Blank
CL4-175 175,000 160,000 CG4001 CG4MUF4 F4G 1.75" 0.348 0.246 None S-6-1/2 / B-0 4 - Slot
CL5-245 245,000 220,000 CG4001 CG4MUF6 F6G 1.75" 0.422 0.281 None S-9 / B-0 4 - Slot
CL-HGS Series
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
CL-HGS 114,000 110,000 CG4001
CG4BMPOF3 F3G 2.00"
0.277 0.266 5880
S-8 / B-0 4 - Slot
CL-HGS*
147,000 145,000 CG4001 CG4BMPOF4 F4G 2.00" 0.316 0.234 5880 S-6 / B-0 4 - Slot
CL-HGS*
189,000 190,000 CG4001 CG4BMPOF4 F4G 2.00" None 0.281 None S-10 / B-1 4 - Slot
* Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F.
Slant/Fin Intrepid
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
TR-30 140,000 140,000 CG4001 CG4SFF3 F3G 1.75" None 0.242 None S-8 / B-0 4 - slot
TR-40 210,000 190,000 CG4001 CG4SFF4 F4G 1.75" None 0.281 None S-10 / B-3 4 - slot
Thermo Dynamics
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
CWL
119,000 130,000 CG4001 CG4TDF4 F4G 3.50" 0.231 0.217
5880
S-10 / B-1 4 - slot
CWL 140,000 145,000 CG4001 CG4TDF4 F4G 3.50" 0.316 0.234
5880
S-10 / B-3 4 - slot
Appliance
Appliance
Input BTU
Beckett
Required
Input BTU
Burner
Chassis
Part #
Air Tube
Combination
Part # Head Insertion
NG
Orifice
Size
LP
Orifice
Size Baffle
Air Settings
Shutter /Band
(see notices)
Air Band / Slot
Number
SFH-3085W 119,000 120,000 CG4001 CG4UTF3
F3G 2.25" 0.316 0.219 Yes S-10 / B-1 4 - slot
SFH-3100W 140,000 140,000 CG4001 CG4UTF3
F3G 2.25" None 0.242 No S-10 / B-0 4 - slot
SFH-4100W 140,000 145,000 CG4001 CG4UTF4 F4G 2.25" 0.316 0.234 Yes S-10 / B-3 4 - slot
Utica Starfire