BEKOMAT 13, 13 CO, 13 CO PN25, 13 CO PN50
Function • Funcionamiento
Functionnement • Funcionamento
Alarm signal via potential-free contact
Mensaje de alarma a través de contacto sin potencial
Signal d'alarme délivré sur le contact sans potentiel
Sinal de alarme via contacto isento de potencial
Switching sequence of valve in alarm mode
Secuencia de actuación de la válvula en el modo de alarma
Séquence d'activation de la vanne en mode Alarme
Sequência de ligação da válvula no modo de alarme
1
3
4
2
1
2 3 65
4
>
<
7,5 sec
1 min 3 min 4 min 4 min
>
>
>
><<
<<
The condensate ows through the feed
line (1) into the BEKOMAT unit and ac-
cumulates in the container (2). A capaci-
tive sensor (3) continuously registers the
liquid level and passes a signal to the
electronic control as soon as the con-
tainer is lled. The pilot valve (4) is then
activated and the diaphragm (5) opens
the outlet line (6) for discharging the
condensate.
When the BEKOMAT unit has been
emptied, the outlet line is closed again
quickly and tightly without wasting com-
pressed air.
Pressing
Short
> 1 min
Effect
Manual drainage
Alarm mode
1
Ready for operation
Voltage is being applied
Discharge procedure
Outlet line is open
Malfunction
Alarm mode is activated
Test
Manual drainage/alarm
The test button is used for checking
correct functioning.
3
4
When the microcontroller registers a
malfunction, the device will automatically
change to the alarm mode. The switching
sequence of the valve (see illustration)
continues until the fault is cleared (auto-
matically or through maintenance). The
red LED ashes as long as the device
is in the alarm mode.
Malfunctioning could be caused by, e.g.:
Mistakes during installation
Dropping below the necessary mini-
mum pressure
Excessive condensate quantities (over-
loading)
Blocked/shut off outlet line
Extreme amount of dirt particles
Frozen piping
If the fault is not cleared within the rst
minute, a fault signal is triggered (see
illustration) which can be picked off as a
potential-free signal via the alarm relay.
(24 VDC version: see pages 10-13)